TOWN OF BOONE, NORTH CAROLINA 2001 SYSTEM PERFORMANCE ANNUAL REPORT Collection System and Wastewater Treatment Plant This report provides performance
information on the Town of Boone sewer collection
system and waste treatment plant in the year 2001. It is required under
the provisions of the Clean Water Act of 1999, House Bill 1160 ratified
on COLLECTION SYSTEM I. General Information Facility Name: Town of Boone Responsible Entity:
Town of Person in Charge: Rick Miller, Superintendent Applicable Permits: None II. System
Description III. Performance Five spills that reached
surface waters occurred in the collection system during the year. In
accordance with State regulations, all were reported to the State of
JIMMY SMITH WASTEWATER TREATMENT PLANT I. General Information
Wastewater is physically screened through two automatic bar screens, then pumped to the highest plant elevation by submersible influent pumps. It then flows through a grit and grease removal unit, then to one of two, 2.4 million-gallon oxidation ditches for biological treatment and ammonia nitrogen removal. Ditch effluent flows to two circular clarifiers, then to four tertiary sand filters for additional solids removal. The final treatment stage is disinfection with ultraviolet light before discharge to the South Fork New River. Solids are processed by a 2-meter belt press and a Class A thermal drier, producing an 87-90% dry product that is distributed to the public for use as fertilizer. III. Performance The plant treated 856 million gallons of wastewater in 2001, down 0.7% from last year. The highest volume month was again March at 79 million gallons, and the lowest was December with 65 million gallons. NPDES Permit: Results for the year 2001 for permit parameters are provided below:
Class A Residuals Permit: The plant had no violations for permit parameter limits for the year. Of 684 tons of residuals produced, 356 tons were distributed to the public for use as fertilizer. Information on proper handling and use was distributed to all recipients. Class B Residuals Permit: No Class B residuals were produced during the year. Air Quality Permit: The plant incurred no air quality violations. All equipment performed in accordance with designed removal rates, and the State Air Quality inspection found no problems. Spills/Overflows: No spills or overflows reaching surface waters occurred during the year. IV. Notification This report is published
on the Town of V. Certification I certify under penalty of law that this report is complete and accurate to the best of my knowledge. I further certify that this report has been made available to the users or customers of the named system and that those users have been notified of its availability.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
__________________________ _______________________ Rick Miller DateSuperintendent Collection and Distribution Systems _________________________ _______________________ Jim Barbee Date SuperintendentWastewater Treatment Plant |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||